§ 866. Trailing cables

437 words·~2 min read·/usc/title-30/section-866

A research copy — for the controlling text, always check the official state or federal source. Not legal advice.

(a)Requirements established for flame resistant cables Trailing cables used in coal mines shall meet the requirements established by the Secretary for flame-resistant cables.
(b)Circuit breakers; markings and visual observation of position of disconnection devices Short-circuit protection for trailing cables shall be provided by an automatic circuit breaker or other no less effective device approved by the Secretary of adequate current-interrupting capacity in each ungrounded conductor. Disconnecting devices used to disconnect power from trailing cables shall be plainly marked and identified and such devices shall be equipped or designed in such a manner that it can be determined by visual observation that the power is disconnected.
(c)Distribution center junctions; safety connections When two or more trailing cables junction to the same distribution center, means shall be provided to assure against connecting a trailing cable to the wrong size circuit breaker.
(d)Temporary splices; usable period; exceptions; quality One temporary splice may be made in any trailing cable. Such trailing cable may only be used for the next twenty-four hour period. No temporary splice shall be made in a trailing cable within twenty-five feet of the machine, except cable reel equipment. Temporary splices in trailing cables shall be made in a workmanlike manner and shall be mechanically strong and well insulated. Trailing cables or hand cables which have exposed wires or which have splices that heat or spark under load shall not be used. As used in this subsection, the term “splice” means the mechanical joining of one or more conductors that have been severed.
(e)Permanent splices; quality When permanent splices in trailing cables are made, they shall be—
(1)mechanically strong with adequate electrical conductivity and flexibility;
(2)effectively insulated and sealed so as to exclude moisture; and
(3)vulcanized or otherwise treated with suitable materials to provide flame-resistant qualities and good bonding to the outer jacket.
(f)Clamping of cables Trailing cables shall be clamped to machines in a manner to protect the cables from damage and to prevent strain on the electrical connections. Trailing cables shall be adequately protected to prevent damage by mobile equipment.
(g)Making and breaking of connections to junction boxes Trailing cable and power cable connections to junction boxes shall not be made or broken under load.
(Pub. L. 91–173, title III, § 306, Dec. 30, 1969, 83 Stat. 779.)
Connections2 cite this · traces to 1
4 references not yet in our index
  • Pub. L. 91–173, title III, § 306
  • 83 Stat. 779
  • Pub. L. 91–173
  • section 509 of Pub. L. 91–173
Citation graph
cites case law
§ 866
Trailing cables
Stat. Comp.×1
U.S.C.×1
Pub. L.Pub. L. 91–173, title III, § 306
Stat.83 Stat. 779
Pub. L.Pub. L. 91–173
Pub. L.section 509 of Pub. L. 91–173
Cites 5Cited by 2 across 2 sources
★   the supreme law of the land   ★
Don't Tread on Me
E Pluribus Unum — out of many, one

"If you don't know your rights, you don't have any."

Marginalia · a citizen's law index
A research desk, not legal advice. Always read the cited source before relying on a summary.
Questions or an issue? support@self-law.org
disclaimerMarginalia is a research index, not a law firm. Nothing on this site is legal, tax, or financial advice and no attorney–client relationship is formed by using it. Statutes, regulations, and case law change; summaries, search results, AI output, and member posts may be incomplete, out of date, or wrong. Any interpretation drawn from material on this site should be validated by a licensed attorney in your jurisdiction before you act on it.