(a)Low-Voltage Dry-Type Distribution Transformers.
(1)The efficiency of a low-voltage, dry-type distribution transformer manufactured on or after January 1, 2007, but before January 1, 2016, shall be no less than that required for the applicable kVA rating in the table below. Low-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating. Single-phase Three-phase kVA % kVA % 1597.71597.0 2598.03097.5 37.598.24597.7 5098.37598.0 7598.5112.598.2 10098.615098.3 16798.722598.5 25098.830098.6 33398.950098.7 75098.8 100098.9 Note 1 to paragraph (a)(1): All efficiency values are at 35 percent per-unit load.
(2)The efficiency of a low-voltage, dry-type distribution transformer manufactured on or after January 1, 2016, but before April 23, 2029, shall be no less than that required for the applicable kVA rating in the following table. Low-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating. Table 2 to Paragraph (a)(1) Single-phase Three-phase kVA kVA 1597.701597.89 2598.003098.23 37.598.204598.40 5098.307598.60 7598.50112.598.74 10098.6015098.83 16798.7022598.94 25098.8030099.02 33398.9050099.14 75099.23 100099.28 Note: All efficiency values are at 35 percent of nameplate-rated load, determined according to the DOE Test Method for Measuring the Energy Consumption of Distribution Transformers under appendix A to this subpart K.
(3)The efficiency of a low-voltage dry-type distribution transformer manufactured on or after April 23, 2029, shall be no less than that required for their kVA rating in the following table. Low-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating. Table 3 to Paragraph (a)(3) Single-phase Three-phase kVA Efficiency (%) kVA Efficiency (%) 1598.391598.31 2598.603098.58 37.598.744598.72 5098.817598.88 7598.95112.598.99 10099.0215099.06 16799.0922599.15 25099.1630099.22 33399.2350099.31 75099.38 100099.42 Note: All efficiency values are at 35 percent of nameplate-rated load, determined according to the DOE Test Method for Measuring the Energy Consumption of Distribution Transformers under appendix A to this subpart K.
(b)Liquid-Immersed Distribution Transformers.
(1)The efficiency of a liquid-immersed distribution transformer manufactured on or after January 1, 2010, but before January 1, 2016, shall be no less than that required for their kVA rating in the table below. Liquid-immersed distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating. Single-phase Three-phase kVA Efficiency (%) kVA Efficiency (%) 1098.621598.36 1598.763098.62 2598.914598.76 37.599.017598.91 5099.08112.599.01 7599.1715099.08 10099.2322599.17 16799.2530099.23 25099.3250099.25 33399.3675099.32 50099.42100099.36 66799.46150099.42 83399.49200099.46 250099.49 Note 3 to paragraph (b)(1): All efficiency values are at 50 percent per-unit load.
(2)The efficiency of a liquid-immersed distribution transformer, including submersible distribution transformers, manufactured on or after January 1, 2016, but before April 23, 2029, shall be no less than that required for their kVA rating in the following table. Liquid-immersed distribution transformers, including submersible distribution transformers, with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating. Table 5 to Paragraph (b)(2) Single-phase Three-phase kVA Efficiency (%) kVA Efficiency (%) 1098.701598.65 1598.823098.83 2598.954598.92 37.599.057599.03 5099.11112.599.11 7599.1915099.16 10099.2522599.23 16799.3330099.27 25099.3950099.35 33399.4375099.40 50099.49100099.43 66799.52150099.48 83399.55200099.51 250099.53 Note: All efficiency values are at 50 percent of nameplate-rated load, determined according to the DOE Test—Procedure, appendix A to this subpart K.
(3)The efficiency of a liquid-immersed distribution transformer, that is not a submersible distribution transformer, manufactured on or after April 23, 2029, shall be no less than that required for their kVA rating in the following table. Liquid-immersed distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating. Table 6 to Paragraph (b)(3) Single-phase Three-phase kVA Efficiency (%) kVA Efficiency (%) 1098.771598.92 1598.883099.06 2599.004599.14 37.599.107599.22 5099.15112.599.29 7599.2315099.33 10099.2922599.38 16799.4630099.42 25099.5150099.38 33399.5475099.43 50099.59100099.46 66799.62150099.51 83399.64200099.53 250099.55 375099.54 500099.53 Note: All efficiency values are at 50 percent of nameplate-rated load, determined according to the DOE Test Method for Measuring the Energy Consumption of Distribution Transformers under appendix A to this subpart K.
(4)The efficiency of a submersible distribution transformer, manufactured on or after April 23, 2029, shall be no less than that required for their kVA rating in the following table. Submersible distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating. Table 7 to Paragraph (b)(4) Single-phase Three-phase kVA Efficiency (%) kVA Efficiency (%) 1098.701598.65 1598.823098.83 2598.954598.92 37.599.057599.03 5099.11112.599.11 7599.1915099.16 10099.2522599.23 16799.3330099.27 25099.3950099.35 33399.4375099.40 50099.49100099.43 66799.52150099.48 83399.55200099.51 250099.53 Note: All efficiency values are at 50 percent of nameplate-rated load, determined according to the DOE Test—Procedure, appendix A to this subpart K.
(c)Medium-Voltage Dry-Type Distribution Transformers.
(1)The efficiency of a medium-voltage dry-type distribution transformer manufactured on or after January 1, 2010, but before January 1, 2016, shall be no less than that required for their kVA and BIL rating in the table below. Medium-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating. Single-phase Three-phase kVA BIL* kVA BIL 20-45 kV 46-95 kV ≥96 kV 20-45 kV 46-95 kV ≥96 kV Efficiency (%) Efficiency (%) Efficiency (%) Efficiency (%) Efficiency (%) Efficiency (%) 1598.1097.861597.5097.18 2598.3398.123097.9097.63 37.598.4998.304598.1097.86 5098.6098.427598.3398.12 7598.7398.5798.53112.598.4998.30 10098.8298.6798.6315098.6098.42 16798.9698.8398.8022598.7398.5798.53 25099.0798.9598.9130098.8298.6798.63 33399.1499.0398.9950098.9698.8398.80 50099.2299.1299.0975099.0798.9598.91 66799.2799.1899.15100099.1499.0398.99 83399.3199.2399.20150099.2299.1299.09 200099.2799.1899.15 250099.3199.2399.20 * BIL means basic impulse insulation level. Note 5 to paragraph (c)(1): All efficiency values are at 50 percent per-unit load.
(2)The efficiency of a medium-voltage dry-type distribution transformer manufactured on or after January 1, 2016, but before April 23, 2029, shall be no less than that required for their kVA and BIL rating in the following table. Medium-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating. Table 9 to Paragraph (c)(2) kVA Single-phase kVA Three-phase BIL 1 BIL 20-45 kV 46-95 kV ≥96 kV 20-45 kV 46-95 kV ≥96 kV Efficiency (%) Efficiency (%) Efficiency (%) Efficiency (%) Efficiency (%) Efficiency (%) 1598.1097.861597.5097.18 2598.3398.123097.9097.63 37.598.4998.304598.1097.86 5098.6098.427598.3398.13 7598.7398.5798.53112.598.5298.36 10098.8298.6798.6315098.6598.51 16798.9698.8398.8022598.8298.6998.57 25099.0798.9598.9130098.9398.8198.69 33399.1499.0398.9950099.0998.9998.89 50099.2299.1299.0975099.2199.1299.02 66799.2799.1899.15100099.2899.2099.11 83399.3199.2399.20150099.3799.3099.21 200099.4399.3699.28 250099.4799.4199.33 1 BIL means basic impulse insulation level. Note: All efficiency values are at 50 percent of nameplate rated load, determined according to the DOE Test Method for Measuring the Energy Consumption of Distribution Transformers under appendix A to this subpart K.
(3)The efficiency of a medium-voltage dry-type distribution transformer manufactured on or after April 23, 2029, shall be no less than that required for their kVA and BIL rating in the following table. Medium-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating. Table 10 to Paragraph (c)(3) kVA Single-phase kVA Three-phase BIL 1 BIL 20-45 kV 46-95 kV ≥96 kV 20-45 kV 46-95 kV ≥96 kV Efficiency (%) Efficiency (%) Efficiency (%) Efficiency (%) Efficiency (%) Efficiency (%) 1598.2998.071597.7597.46 2598.5098.313098.1197.87 37.598.6498.474598.2998.07 5098.7498.587598.5098.32 7598.8698.7198.68112.598.6798.52 10098.9498.8098.7715098.7998.66 16799.0698.9598.9222598.9498.8298.71 25099.1699.0699.0230099.0498.9398.82 33399.2399.1399.0950099.1899.0999.00 50099.3099.2199.1875099.2999.2199.12 66799.3499.2699.24100099.3599.2899.20 83399.3899.3199.28150099.4399.3799.29 200099.4999.4299.35 250099.5299.4799.40 375099.5099.4499.40 500099.4899.4399.39 1 BIL means basic impulse insulation level/ Note: All efficiency values are at 50 percent of nameplate rated load, determined according to the DOE Test Method for Measuring the Energy Consumption of Distribution Transformers under appendix A to this subpart K.
(d)Mining Distribution Transformers. [Reserved]
(e)Severability. The provisions of paragraphs
(a)through
(d)of this section are separate and severable from one another. Should a court of competent jurisdiction hold any provision(s) of this section to be stayed or invalid, such action shall not affect any other provision of this section. [78 FR 23433, Apr. 18, 2013, as amended at 86 FR 51252, Sept. 14, 2021; 89 FR 30040, Apr. 22, 2024]
Connections66 cite this
★   the supreme law of the land   ★
Don't Tread on Me
E Pluribus Unum — out of many, one

"If you don't know your rights, you don't have any."

Marginalia · a citizen's law index
A research desk, not legal advice. Always read the cited source before relying on a summary.
Questions or an issue? support@self-law.org
disclaimerMarginalia is a research index, not a law firm. Nothing on this site is legal, tax, or financial advice and no attorney–client relationship is formed by using it. Statutes, regulations, and case law change; summaries, search results, AI output, and member posts may be incomplete, out of date, or wrong. Any interpretation drawn from material on this site should be validated by a licensed attorney in your jurisdiction before you act on it.