Tap any paragraph to write a margin note. Your notes collect in the Desk below the text and file under cases with @. The side-by-side margin rail opens on a larger screen.

Code · Utah · Title 15A — State Construction and Fire Codes Act · Chapter 3

Superseded 7/1/2026

408 words·~2 min read·/ut/title-15a/chapter-3/7-15

A research copy — for the controlling text, always check the official state or federal source. Not legal advice.

Effective 7/1/2023
Superseded 7/1/2026
15A-3-304. Amendments to Chapter 4 of IPC.
(1)In IPC, Table 403.1, the following changes are made:
(a)In row number "3", for in the field for "OTHER", a new footnote h is added.
(b)In row number "5", for "Adult day care and child day care" occupancy, in the field for "OTHER", a new footnote h is added.
(c)Footnote f is deleted and replaced with the following: "FOOTNOTE f: The required number and type of plumbing fixtures for outdoor public swimming pools shall be in accordance with Utah Administrative Code, R392-302 Design, Construction and Operation of Public Pools."
(d)A new footnote g is added as follows: "FOOTNOTE: g: When provided, in public toilet facilities, there shall be an equal number of diaper changing facilities in male toilet rooms and female toilet rooms. Diaper changing facilities shall meet the requirements of ASTM F2285-04
(2010)Standard Consumer Safety Performance Specifications for Diaper Changing Tables for Commercial Use."
(e)A new footnote h is added to the table as follows: "FOOTNOTE h: Non-residential child care facilities shall comply with the additional sink requirements of Utah Administrative Code, R381-60-9, Hourly Child Care Centers, R381-70-9, Out of School Time Child Care Programs, and R381-100-9, Child Care Centers."
(2)In IPC, Section 405.3.4, the following sentence is added after the first sentence: "For facilities designed for use by all genders in the same room, the partitions of the stalls shall extend from the floor to the ceiling."
(3)In IPC, Section 405.3.5, the following sentence is added at the end of the first paragraph: "For facilities designed for use by all genders in the same room, the partitions of the stalls shall extend from the floor to the ceiling."
(4)A new IPC, Section 406.3, is added as follows: "406.3 Automatic clothes washer safe pans. Safe pans, when installed under automatic clothes washers, shall be installed in accordance with Section 504.7."
(5)A new IPC, Section 413.5, is added as follows: "413.5 Public toilet rooms. All public toilet rooms shall be equipped with at least one floor drain."
(6)A new IPC, Section 413.6, is added as follows: "Prohibition of motor vehicle waste disposal wells. New and existing motor vehicle waste disposal wells are prohibited. A motor vehicle waste disposal well associated with a single family residence is not subject to this prohibition."
(7)IPC, Section 423.3, is deleted.
Amended by Chapter 209 , 2023 General Session
★   the supreme law of the land   ★
Don't Tread on Me
E Pluribus Unum — out of many, one

"If you don't know your rights, you don't have any."

Marginalia · a citizen's law index
A research desk, not legal advice. Always read the cited source before relying on a summary.
Questions or an issue? support@self-law.org
disclaimerMarginalia is a research index, not a law firm. Nothing on this site is legal, tax, or financial advice and no attorney–client relationship is formed by using it. Statutes, regulations, and case law change; summaries, search results, AI output, and member posts may be incomplete, out of date, or wrong. Any interpretation drawn from material on this site should be validated by a licensed attorney in your jurisdiction before you act on it.