§ 183.588. Slosh test.

148 words·~1 min read·/us/cfr/t33/s§ 183.588·

A research copy — for the controlling text, always check the official state or federal source. Not legal advice.

A fuel tank is tested by performing the following procedures in the following order:
(a)Perform the static pressure test under § 183.580.
(b)Perform the pressure impulse test under § 183.586.
(c)Secure the tank to the platform of a tank rocker assembly.
(d)Fill the tank to one-half capacity with water.
(e)Cap and seal each opening in the tank.
(f)Apply 500,000 cycles or rocking motion 15 degrees to each side of the tank centerline at the rate of 15 to 20 cycles a minute. The axis of rotation of the rocker and fuel tank must be perpendicular to the centerline of the tank length at a level six inches or less above or below the tank's bottom.
(g)Perform the static pressure test under § 183.580. \[CGD 74-209, 42 FR 5950, Jan. 31, 1977, as amended by USCG-1999-5832, 64 FR 34716, June 29, 1999\]
★   the supreme law of the land   ★
Don't Tread on Me
E Pluribus Unum — out of many, one

"If you don't know your rights, you don't have any."

Marginalia · a citizen's law index
A research desk, not legal advice. Always read the cited source before relying on a summary.
Questions or an issue? support@self-law.org
disclaimerMarginalia is a research index, not a law firm. Nothing on this site is legal, tax, or financial advice and no attorney–client relationship is formed by using it. Statutes, regulations, and case law change; summaries, search results, AI output, and member posts may be incomplete, out of date, or wrong. Any interpretation drawn from material on this site should be validated by a licensed attorney in your jurisdiction before you act on it.