§ 154.2109. Vapor recovery and vapor destruction units.

510 words·~2 min read·/us/cfr/t33/s§ 154.2109·

A research copy — for the controlling text, always check the official state or federal source. Not legal advice.

Paragraphs (a), (b), and
(e)of this section apply only to facilities collecting vapors of flammable, combustible, or non-high flash point liquid cargoes.
(a)The inlet to a vapor recovery unit that receives vapor that has not been inerted, enriched, or diluted in accordance with 33 CFR 154.2107 must be fitted with a detonation arrester.
(b)The inlet to a vapor destruction unit must---
(1)Have a liquid seal that meets the requirements of paragraph
(e)of this section, except as specified by paragraph (b)(3) of this section; and
(2)Have two quick-closing stop valves installed in the vapor line. One of them must be installed upstream of the detonation arrester required by paragraph (c)(2) of this section. The quick-closing stop valves must---
(i)Close within 30 seconds after detection of a condition that requires the closing of these two quick-closing stop valves by a control component required by this subpart for a vapor control system
(VCS)with a vapor destruction unit;
(ii)Close automatically if the control signal is lost;
(iii)Have a local valve position indicator or be designed so that the valve position is readily determined from the valve handle or valve stem position; and
(iv)If the valve seat is fitted with resilient material, be a Category A valve as defined by 46 CFR 56.20-15 and not allow appreciable leakage when the resilient material is damaged or destroyed; and
(3)Instead of a liquid seal as required by paragraph (b)(1) of this section, have the following:
(i)An anti-flashback burner accepted by the Commandant and installed at each burner within the vapor destruction unit; and
(ii)A differential pressure sensor that activates the quick-closing stop valves as required by paragraph (b)(2) of this section upon sensing a reverse flow condition.
(c)A vapor destruction unit must---
(1)Not be within 30 meters (98.8 feet) of any tank vessel berth or mooring at the facility;
(2)Have a detonation arrester fitted in the inlet vapor line; and
(3)Activate an alarm that satisfies the requirements of 33 CFR 154.2100(e) and shut down when a flame is detected on the detonation arrester.
(d)When a vapor destruction unit shuts down or has a flame-out condition, the vapor destruction unit control system must---
(1)Activate and close the quick-closing stop valves required by paragraph (b)(2) of this section;
(2)Close the remotely operated cargo vapor shutoff valve required by 33 CFR 154.2101(a); and
(3)Automatically shut down any vapor-moving devices installed in the VCS.
(e)If a liquid seal is installed at the inlet to a vapor destruction unit, then---
(1)The liquid used in the liquid seal must be compatible with the vapors being controlled;
(2)For partially or totally soluble cargoes that can polymerize in solution, there must be an adequate amount of inhibitor in the liquid seal;
(3)The liquid seal must be compatible with the design of the VCS and must not contribute to the flammability of the vapor stream; and
(4)The liquid seal must have a low-level alarm and a low-low level shutdown.
Connections17 cite this · traces to 3
★   the supreme law of the land   ★
Don't Tread on Me
E Pluribus Unum — out of many, one

"If you don't know your rights, you don't have any."

Marginalia · a citizen's law index
A research desk, not legal advice. Always read the cited source before relying on a summary.
Questions or an issue? support@self-law.org
disclaimerMarginalia is a research index, not a law firm. Nothing on this site is legal, tax, or financial advice and no attorney–client relationship is formed by using it. Statutes, regulations, and case law change; summaries, search results, AI output, and member posts may be incomplete, out of date, or wrong. Any interpretation drawn from material on this site should be validated by a licensed attorney in your jurisdiction before you act on it.