§ 75.1107-9. Dry chemical devices; capacity; minimum requirements.

442 words·~2 min read·/us/cfr/t30/s§ 75.1107-9·

A research copy — for the controlling text, always check the official state or federal source. Not legal advice.

(a)Dry chemical fire extinguishing systems used on underground equipment shall be of the multipurpose powder-type and shall include the following:
(1)The system including all hose and nozzles shall be protected against the entrance of moisture, dust, or dirt;
(2)The system shall be guarded against damage during operation of the equipment protected;
(3)Hose and pipe shall be as short as possible; the distance between the chemical container and furthest nozzle shall not exceed 50 feet;
(4)Hose, piping, and fittings between the actuator and the chemical container shall have a bursting pressure of 500 pounds per square inch
(gage)or higher; the hose, piping, and fittings between the chemical container and the nozzles shall have a bursting pressure of 300 pounds per square inch
(gage)or higher and
(5)The system shall discharge in 1 minute or less, for quantities less than 50 pounds (nominal) 1 and in less than 2 minutes for quantities more than 50 pounds; 1 Many dry chemical systems were originally designed for sodium bicarbonate before all-purpose chemical (ammonium phosphate) was shown to be more effective. Sodium bicarbonate is denser than ammonium phosphate; hence, for example, a 50-pound system designed for the sodium bicarbonate will hold slightly more by weight than all-purpose dry chemical (ammonium phosphate) by weight. The word "nominal" is used in § 75.1107-9 to express the approximate weight in pounds of all-purpose dry chemical.
(b)On unattended underground equipment, the number of pounds of dry chemical employed by the system shall be not less than 1 pound per square foot of top surface area of the equipment; however, the minimum amount in any system shall be 20 pounds (nominal). The discharge shall be directed into and on potentially hazardous locations of the equipment.
(c)On attended underground equipment, the number of pounds (nominal) employed by the system shall equal 5 times the total number of hazardous locations; however, the minimum amount in any system shall not be less than the following, except that systems on haulage vehicles installed prior to the effective date of this section may contain 20 pounds (nominal). Type of equipment Dry chemical pounds (nominal)
(1)Cutting machines ``` ``` 40
(2)Continuous miners ``` ``` 40
(3)Haulage vehicles ``` ``` 30
(4)All other attended equipment ``` ``` 20 ``` ``` ``` ``` ``` ```
(d)The amount of dry chemical discharged into the cable reel compartments of attended underground equipment shall be approximately 25 percent of the total amount required to be discharged by the system; however, the quantity discharged into cable reel compartments need not exceed 10 pounds. ``` \[37 FR 15302, July 29, 1972\]
★   the supreme law of the land   ★
Don't Tread on Me
E Pluribus Unum — out of many, one

"If you don't know your rights, you don't have any."

Marginalia · a citizen's law index
A research desk, not legal advice. Always read the cited source before relying on a summary.
Questions or an issue? support@self-law.org
disclaimerMarginalia is a research index, not a law firm. Nothing on this site is legal, tax, or financial advice and no attorney–client relationship is formed by using it. Statutes, regulations, and case law change; summaries, search results, AI output, and member posts may be incomplete, out of date, or wrong. Any interpretation drawn from material on this site should be validated by a licensed attorney in your jurisdiction before you act on it.