§ 7.68. Firing line terminals test.
71 words·~1 min read·
/us/cfr/t30/s§ 7.68·A research copy — for the controlling text, always check the official state or federal source. Not legal advice.
(a)Test procedures.
(1)The contact resistance through each firing line terminal shall be determined.
(2)A 10-pound pull shall be applied to a No. 18 gauge wire that has been connected to each firing line terminal according to the manufacturer's instructions.
(b)Acceptable performance.
(1)The contact resistance shall not be greater than 1 ohm.
(2)The No. 18 gauge wire shall not become disconnected from either firing line terminal.