(a)Each extinguishing agent container must have a pressure relief to prevent bursting of the container by excessive internal pressures.
(b)The discharge end of each discharge line from a pressure relief connection must be located so that discharge of the fire extinguishing agent would not damage the rotorcraft. The line must also be located or protected to prevent clogging caused by ice or other foreign matter.
(c)There must be a means for each fire extinguishing agent container to indicate that the container has discharged or that the charging pressure is below the established minimum necessary for proper functioning.
(d)The temperature of each container must be maintained, under intended operating conditions, to prevent the pressure in the container from—
(1)Falling below that necessary to provide an adequate rate of discharge; or
(2)Rising high enough to cause premature discharge. (Secs. 313(a), 601, and 603, 72 Stat. 759, 775, 49 U.S.C. 1354(a), 1421, and 1423; sec. 6(c), 49 U.S.C. 1655 (c)) [Doc. No. 5084, 29 FR 16150, Dec. 3, 1964, as amended by Amdt. 29-13, 42 FR 15047, Mar. 17, 1977]