§ 460.102. Building thermal envelope requirements.

604 words·~3 min read·/us/cfr/t10/s§ 460.102·

A research copy — for the controlling text, always check the official state or federal source. Not legal advice.

(a)Compliance options. The building thermal envelope must meet either the prescriptive requirements of paragraph
(b)of this section or the performance requirements of paragraph
(c)of this section.
(b)Prescriptive requirements.
(1)The building thermal envelope must meet the applicable minimum R-value (nominal value of insulation), and the glazing maximum U-factor and SHGC, requirements set forth in table 1 to § 460.102(b)(1) and table 2 to § 460.102(b)(2) or component U-values set forth in table 3 to § 460.102(b)(5) and table 4 to § 460.102(b)(5). Table 1 to § 460.102(b)(1)—Tier 1 Building Thermal Envelope Prescriptive Requirements Climate zone Exterior wall insulation R-value Exterior ceiling insulation R-value Exterior floor insulation R-value Window U-factor Skylight U-factor Door U-factor Glazed fenestration SHGC 11322221.080.750.400.7 21322190.50.550.400.6 31922220.350.550.40Not applicable. Table 2 to § 460.102(b)(1)—Tier 2 Building Thermal Envelope Prescriptive Requirements Climate zone Exterior wall insulation R-value Exterior ceiling insulation R-value Exterior floor insulation R-value Window U-factor Skylight U-factor Door U-factor Glazed fenestration SHGC 11330130.320.750.400.33 22130190.300.550.400.25 32138300.300.550.40Not applicable.
(2)For the purpose of compliance with the exterior ceiling insulation R-value requirement of paragraph (b)(1) of this section, the truss heel height must be a minimum of 5.5 inches at the outside face of each exterior wall.
(3)A combination of R-21 batt insulation and R-14 blanket insulation may be used for the purpose of compliance with the floor insulation R-value requirement of table 2 to § 460.102(b)(1), Climate Zone 3.
(4)An individual skylight that has an SHGC that is less than or equal to 0.30 is not subject to the glazed fenestration SHGC requirements established in paragraph (b)(1) of this section. Adapted from section R402 of the 2021 IECC.
(5)U-factor alternatives to R-value requirements. Compliance with the applicable requirements in paragraph (b)(1) of this section may be determined using the applicable maximum U-factor values set forth in table 3 to § 460.102(b)(5) and table 4 to § 460.102(b)(5), which reflect the thermal transmittance of the component, excluding fenestration, and not just the insulation of that component, as an alternative to the minimum nominal R-value requirements set forth in table 1 to § 460.102(b)(1) and table 2 to § 460.102(b)(1), respectively. Table 3 to § 460.102(b)(5)—U-Factor Alternatives to Tier 1 R-Value Requirements Climate zone Exterior ceiling U-factor Exterior wall U-factor Exterior floor U-factor 10.0610.0940.049 20.0610.0940.056 30.0610.0680.049 Table 4 to § 460.102(b)(5)—U-Factor Alternatives to Tier 2 R-Value Requirements Climate zone Exterior ceiling U-factor Exterior wall U-factor Exterior floor U-factor 10.0430.0940.078 20.0430.0630.056 30.0370.0630.032
(c)Performance requirements.
(1)The building thermal envelope must have a Uo that is less than or equal to the applicable value specified in table 5 to § 460.102(c)(1) and table 6 to § 460.102(c)(1). Table 5 to § 460.102(c)(1)—Tier 1 Building Thermal Envelope Performance Requirements Climate zone Single-section Uo 10.110 20.091 30.074 Table 6 to § 460.102(c)(1)—Tier 2 Building Thermal Envelope Performance Requirements Climate zone Multi-section Uo 10.082 20.066 30.055
(2)Area-weighted average vertical fenestration U-factor must not exceed 0.48 in Climate Zone 2 or 0.40 in Climate Zone 3. Adapted from section R402 of the 2021 IECC.
(3)Area-weighted average skylight U-factor must not exceed 0.75 in Climate Zone 2 and Climate Zone 3. Adapted from section R402 of the 2021 IECC.
(4)Windows, skylights and doors containing more than 50 percent glazing by area must satisfy the SHGC requirements established in paragraph (b)(1) of this section on the basis of an area-weighted average. Adapted from section R402 of the 2021 IECC.
(d)[Reserved].
(e)Determination of compliance with paragraph
(c)of this section.
(1)Uo must be determined in accordance with Overall U-Values and Heating/Cooling Loads—Manufactured Homes (incorporated by reference; see § 460.3)
(2)[Reserved]
Connections10 cite this
Citation graph
cites case law
§ 460.102
Building thermal envelope requirements.
Fed. Reg.×10
Cites 0Cited by 10 across 1 source
★   the supreme law of the land   ★
Don't Tread on Me
E Pluribus Unum — out of many, one

"If you don't know your rights, you don't have any."

Marginalia · a citizen's law index
A research desk, not legal advice. Always read the cited source before relying on a summary.
Questions or an issue? support@self-law.org
disclaimerMarginalia is a research index, not a law firm. Nothing on this site is legal, tax, or financial advice and no attorney–client relationship is formed by using it. Statutes, regulations, and case law change; summaries, search results, AI output, and member posts may be incomplete, out of date, or wrong. Any interpretation drawn from material on this site should be validated by a licensed attorney in your jurisdiction before you act on it.