§ 431.86. Uniform test method for the measurement of energy efficiency of commercial packaged boilers.

244 words·~1 min read·/us/cfr/t10/s§ 431.86·

A research copy — for the controlling text, always check the official state or federal source. Not legal advice.

(a)Scope. This section provides test procedures, pursuant to the Energy Policy and Conservation Act (EPCA), as amended, which must be followed for measuring the combustion efficiency and/or thermal efficiency of a gas- or oil-fired commercial packaged boiler.
(b)Testing and Calculations. Determine the thermal efficiency or combustion efficiency of commercial packaged boilers by conducting the appropriate test procedure(s) indicated in Table 1 of this section. Table 1—Test Requirements for Commercial Packaged Boiler Equipment Classes Equipment category Subcategory Certified rated input Btu/h Standards efficiency metric (§ 431.87) Test procedure (corresponding to standards efficiency metric required by § 431.87) Hot WaterGas-fired≥300,000 and ≤2,500,000Thermal EfficiencyAppendix A, Section 2. Hot WaterGas-fired>2,500,000Combustion EfficiencyAppendix A, Section 3. Hot WaterOil-fired≥300,000 and ≤2,500,000Thermal EfficiencyAppendix A, Section 2. Hot WaterOil-fired>2,500,000Combustion EfficiencyAppendix A, Section 3. SteamGas-fired (all*)≥300,000 and ≤2,500,000Thermal EfficiencyAppendix A, Section 2. SteamGas-fired (all*)>2,500,000 and ≤5,000,000Thermal EfficiencyAppendix A, Section 2. >5,000,000Thermal EfficiencyAppendix A, Section 2. OR Appendix A, Section 3 with Section 2.4.3.2. SteamOil-fired≥300,000 and ≤2,500,000Thermal EfficiencyAppendix A, Section 2. SteamOil-fired>2,500,000 and ≤5,000,000Thermal EfficiencyAppendix A, Section 2. >5,000,000Thermal EfficiencyAppendix A, Section 2. OR Appendix A, Section 3. with Section 2.4.3.2. * Equipment classes for commercial packaged boilers as of July 22, 2009 (74 FR 36355) distinguish between gas-fired natural draft and all other gas-fired (except natural draft).
(c)Field Tests. The field test provisions of appendix A may be used only to test a unit of commercial packaged boiler with rated input greater than 5,000,000 Btu/h. [81 FR 89305, Dec. 9, 2016]
Connections38 cite this
★   the supreme law of the land   ★
Don't Tread on Me
E Pluribus Unum — out of many, one

"If you don't know your rights, you don't have any."

Marginalia · a citizen's law index
A research desk, not legal advice. Always read the cited source before relying on a summary.
Questions or an issue? support@self-law.org
disclaimerMarginalia is a research index, not a law firm. Nothing on this site is legal, tax, or financial advice and no attorney–client relationship is formed by using it. Statutes, regulations, and case law change; summaries, search results, AI output, and member posts may be incomplete, out of date, or wrong. Any interpretation drawn from material on this site should be validated by a licensed attorney in your jurisdiction before you act on it.