Tap any paragraph to write a margin note. Your notes collect in the Desk below the text and file under cases with @. The side-by-side margin rail opens on a larger screen.

Code · South Dakota · Title 34 · Chapter 34-38

34-38-30. Impermissible methods for dispensing fuel from aboveground tank--Equipment requirements as to tanks--Failure to comply as misdemeanor.

324 words·~1 min read·/sd/title-34/chapter-34-38/34-38-30

A research copy — for the controlling text, always check the official state or federal source. Not legal advice.

No person may dispense fuel from an aboveground storage tank by either gravity flow or pressurization of the tank. The owner of an aboveground storage tank shall prevent the release of liquid from the tank by syphon flow.
If an aboveground storage tank is at an elevation that produces a gravity head on the dispensing device, the tank outlet shall be equipped with a device such as a normally - closed solenoid valve that will prevent gravity flow from the tank to the dispenser. This device shall be located adjacent to and downstream of the outlet valve. The device shall be installed and adjusted so that liquid cannot flow by gravity from the tank to the dispenser if the piping or hose fails.
If a submersible pump system is used, a listed rigidly anchored emergency shutoff valve, incorporating a fusible link or other thermally actuated device which is designed to close automatically in the event of severe impact or fire exposure, shall be installed in accordance with the manufacturer's instructions in the supply line at the base of each individual island - type dispenser or at the inlet of each overhead dispensing device. An emergency shutoff valve incorporating a slip joint feature may not be used. The automatic closing feature of this valve shall be checked at the time of initial installation and at least once a year thereafter by manually tripping the hold - open linkage.
If a suction pump - type dispensing device is used, a listed, vacuum - actuated shut - off valve, with a shear section, or an equivalent - type valve shall be installed directly beneath each dispensing device.
Shut - off and check valve shall be equipped with a pressure - relieving device to relieve the pressure generated by thermal expansion back to the tank and piping shall be routed so that exposure to physical damage is minimized.
A violation of this section is a Class 2 misdemeanor.
★   the supreme law of the land   ★
Don't Tread on Me
E Pluribus Unum — out of many, one

"If you don't know your rights, you don't have any."

Marginalia · a citizen's law index
A research desk, not legal advice. Always read the cited source before relying on a summary.
Questions or an issue? support@self-law.org
disclaimerMarginalia is a research index, not a law firm. Nothing on this site is legal, tax, or financial advice and no attorney–client relationship is formed by using it. Statutes, regulations, and case law change; summaries, search results, AI output, and member posts may be incomplete, out of date, or wrong. Any interpretation drawn from material on this site should be validated by a licensed attorney in your jurisdiction before you act on it.