15A-4-105. Amendments to IBC applicable to Park City Corporation or Park City Fire District.

421 words·~2 min read·/ut/title-15a/chapter-4/15a-4-105

A research copy — for the controlling text, always check the official state or federal source. Not legal advice.

Effective 5/9/2017
15A-4-105. Amendments to IBC applicable to Park City Corporation or Park City Fire District.
(1)The following amendment is adopted as an amendment to the IBC for the Park City Corporation, in IBC, Section 3409.2, exception 3, is modified to read as follows: "3. Designated as historic under a state or local historic preservation program."
(2)The following amendments are adopted as amendments to the IBC for the Park City Corporation and Park City Fire District:
(a)IBC, Section (F)903.2, is deleted and replaced with the following: "(F)903.2 Where required. Approved automatic sprinkler systems in new buildings and structures shall be provided in the location described in this section.
1. All new construction having more than 6,000 square feet on any one floor, except R-3 occupancy.
2. All new construction having more than two
(2)stories, except R-3 occupancy.
3. All new construction in the Historic Commercial Business zone district, regardless of occupancy.
4. All new construction and buildings in the General Commercial zone district where there are side yard setbacks or where one or more side yard setbacks is less than two and one half (2.5) feet per story of height.
5. All existing building within the Historic District Commercial Business zone."; and
(b)In IBC, Table 1505.1, new footnotes d and e are added as follows: "d. Wood roof covering assemblies are prohibited in R-3 occupancies in areas with a combined rating of more than 11 using Tables 1505.1.1 and 1505.1.2 with a score of 9 for weather factors.
e. Wood roof covering assemblies shall have a Class A rating in occupancies other than R-3 in areas with a combined rating of more than 11 using Tables 1505.1.1 and 1505.1.2 with a score of 9 for weather factors. The owner of the building shall enter into a written and recorded agreement that the Class A rating of the roof covering assembly will not be altered through any type of maintenance process.
TABLE 1505.1.1
WILDFIRE HAZARD SEVERITY SCALE
RATING SLOPE VEGETATION
1 less than or equal to 10% Pinion-juniper
2 10.1 - 20% Grass-sagebrush
3 greater than 20% Mountain brush or softwoods
TABLE 1505.1.2
PROHIBITION/ALLOWANCE OF WOOD ROOFING
Rating R-3 Occupancy All Other Occupancies
Less than or equal to 11 Wood roof covering assemblies per Table 1505.1 are allowed Wood roof covering assemblies per Table 1505.1 are allowed
Greater than or equal to 12 Wood roof covering is prohibited Wood roof covering assemblies with a Class A rating are allowed"
Amended by Chapter 341 , 2017 General Session
★   the supreme law of the land   ★
Don't Tread on Me
E Pluribus Unum — out of many, one

"If you don't know your rights, you don't have any."

Marginalia · a citizen's law index
A research desk, not legal advice. Always read the cited source before relying on a summary.
Questions or an issue? support@self-law.org
disclaimerMarginalia is a research index, not a law firm. Nothing on this site is legal, tax, or financial advice and no attorney–client relationship is formed by using it. Statutes, regulations, and case law change; summaries, search results, AI output, and member posts may be incomplete, out of date, or wrong. Any interpretation drawn from material on this site should be validated by a licensed attorney in your jurisdiction before you act on it.