15A-3-309. Amendments to Chapter 9 of IPC.

125 words·~1 min read·/ut/title-15a/chapter-3/15a-3-309

A research copy — for the controlling text, always check the official state or federal source. Not legal advice.

Effective 7/1/2023
15A-3-309. Amendments to Chapter 9 of IPC.
(1)In IPC, Section 903.1.1, when the number of inches is to be specified, "12 inches (304.8mm)" is inserted.
(2)In IPC, a new Section 903.7 is added as follows: "903.7 Extension through a wall. Vents extending through the wall shall terminate not less than 12 inches from the wall with an elbow pointing downward."
(3)In IPC, Section 905.4, the following sentence is added at the end of the paragraph: "Horizontal dry vents below the flood level rim shall be permitted for floor drain, floor sink, and bath tub installations when installed in accordance with Sections 702.2, 905.2 and 905.3 and provided with a wall clean out."
Amended by Chapter 209 , 2023 General Session
★   the supreme law of the land   ★
Don't Tread on Me
E Pluribus Unum — out of many, one

"If you don't know your rights, you don't have any."

Marginalia · a citizen's law index
A research desk, not legal advice. Always read the cited source before relying on a summary.
Questions or an issue? support@self-law.org
disclaimerMarginalia is a research index, not a law firm. Nothing on this site is legal, tax, or financial advice and no attorney–client relationship is formed by using it. Statutes, regulations, and case law change; summaries, search results, AI output, and member posts may be incomplete, out of date, or wrong. Any interpretation drawn from material on this site should be validated by a licensed attorney in your jurisdiction before you act on it.