49-47-1. Definitions.
270 words·~1 min read·
/sd/title-49/chapter-49-47/49-47-1A research copy — for the controlling text, always check the official state or federal source. Not legal advice.
Terms used in this chapter mean:
(1)"Adequate remediation," corrective action by an electric utility that results in, and is reasonably likely to sustain, a reduction of stray current or voltage attributable to the electric utility's distribution system of fifty percent or less of the preventive action level;
(2)"Commission," the Public Utilities Commission;
(3)"Cow contact points," any two electrically conductive points that a dairy cow may, in its normal environment, unavoidably and simultaneously contact;
(4)"Electric utility" or "utility," an electric utility as defined in § 49-34A-1 ;
(5)"Preventive action level," stray current or voltage that is either:
(a)A steady-state, root mean square (rms), alternating current
(AC)of 2.0 milliamp
(mA)or more through a 500 ohm resistor connected between cow contact points, as measured by a true rms meter; or
(b)A steady-state, rms, AC voltage of 1.0 volts or more, across (in parallel with) a 500 ohm resistor connected between cow contact points, as measured by a true rms meter;
(6)"Steady-state," the value of a current or voltage after an amount of time where all transients have decayed to a negligible value;
(7)"Stray current or voltage,":
(a)Any steady-state, 60 hertz
(Hz)(including harmonics thereof), root mean square (rms), alternating current
(AC)of less than 20 milliamp
(mA)through a 500 ohm resistor connected between cow contact points, as measured by a true rms meter; or
(b)Any steady-state, 60 Hz (including harmonics thereof), rms, AC voltage of less than 10 volts, across (in parallel with) a 500 ohm resistor connected between cow contact points, as measured by a true rms meter.