Tap any paragraph to write a margin note. Your notes collect in the Desk below the text and file under cases with @. The side-by-side margin rail opens on a larger screen.

Code · Nevada · CHAPTER 477 - STATE FIRE MARSHAL

NRS 477.150 Fire sprinklers; elevators; posting of floor numbers and route for evacuation; heating, ventilating, air-conditioning and paging systems.

315 words·~1 min read·/nv/chapter-477-state-fire-marshal/477-150

A research copy — for the controlling text, always check the official state or federal source. Not legal advice.

NRS 477.150 Fire sprinklers; elevators; posting of floor numbers and route for evacuation; heating, ventilating, air-conditioning and paging systems. The owner or operator of every hotel, motel, office, apartment building or condominium where human occupancy is permitted on floors which are more than 55 feet above the lowest level of ground accessible to vehicles of a fire department, shall:
1. Equip each exit corridor of the building with fire sprinklers as required by regulations of the State Fire Marshal;
2. Except in a condominium, equip each room with at least one fire sprinkler above each door opening into an exit corridor of the building;
3. Equip every elevator so as to permit it to be recalled automatically, in compliance with section A 17.1 of the 1978 edition of the American National Standards Institute and section 211.3 of the 1981 amendments to that edition, to the first floor or, if necessary, to any other floor of the building not affected by fire;
4. Post the number of each floor in every stairwell and in every lobby adjacent to an elevator;
5. Equip the heating, ventilating and air-conditioning system with an automatic device to shut it off as prescribed in section 1009 of the 1979 edition of the Uniform Mechanical Code , and with an additional smoke detector as required by the 1978 edition of National Fire Protection Association Standard 90A; and
6. In each room primarily used for sleeping, except in a condominium:
(a)Post in a prominent location an explanation of the route to use for evacuation of the building; and
(b)Install a paging alarm system which conforms to the regulations of the State Fire Marshal, to permit vocal warning and instructions to the occupants.
7. In a condominium, install in the common areas a paging alarm system meeting the requirements of paragraph
(b)of subsection 6, with a sound level of 80 decibels.
★   the supreme law of the land   ★
Don't Tread on Me
E Pluribus Unum — out of many, one

"If you don't know your rights, you don't have any."

Marginalia · a citizen's law index
A research desk, not legal advice. Always read the cited source before relying on a summary.
Questions or an issue? support@self-law.org
disclaimerMarginalia is a research index, not a law firm. Nothing on this site is legal, tax, or financial advice and no attorney–client relationship is formed by using it. Statutes, regulations, and case law change; summaries, search results, AI output, and member posts may be incomplete, out of date, or wrong. Any interpretation drawn from material on this site should be validated by a licensed attorney in your jurisdiction before you act on it.